Finance Committee - Agenda - 6/7/2017 - P642

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P642

16900-3
CONTROLS

X, Allen-Bradley or approved equal. Relays with 30 ampere contact rating shall
be Square D, Class 8501, Type C or equal.

Finance Committee - Agenda - 6/7/2017 - P641

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P641

16900-2
CONTROLS

b. Push buttons shall have removable inserts in eight different colors for
function color coding. Push-button inserts shall be removable from the
front of the control station without disturbing the wiring or mounting of the
control units.

Finance Committee - Agenda - 6/7/2017 - P640

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P640

PART 1 - GENERAL

16900-1

SECTION 16900

CONTROLS

1.1 DESCRIPTION
A. Provide and install all panel and enclosure components and appurtenances as shown
on the Drawings as Local Control Stations as specified herein. All components shall
meet NEMA ratings as indicated on drawing E-1 for the specific area where they are
to be installed.

1.2 SUBMITTALS TO THE ENGINEER
A. Shop drawings are required for all items provided under this Section. Submittals
shall be in accordance with Sections 01340 and 16010.

Finance Committee - Agenda - 6/7/2017 - P639

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P639

16500-4
LIGHTING

PART 3 - EXECUTION

3.1

3.2

INSTALLATION

A. Refer to the contract documents for fixture mounting heights.

B. Mount fixtures in true vertical and horizontal alignment.

C. Fixture locations shown on the drawings are diagrammatic only. They are shown for
quantity and approximate locations only. Adjust the location of any lighting fixture
as required to avoid interferences with existing conditions, equipment, and of the
work of other trades.

Finance Committee - Agenda - 6/7/2017 - P638

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P638

16500-3
LIGHTING

Ballasts

1.

Ballasts shall be designed for continuous operation within the fixture provided
and utilizing the lamp(s) specified without overheating or any other detrimental
affects.

Ballasts shall be quiet in operation and of the lowest noise level generally
available. Fixtures shall suppress ballast noise. Ballasts considered by the
Engineer to have objectionable hum or noise shall be replaced immediately at
no additional cost.

Finance Committee - Agenda - 6/7/2017 - P637

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P637

16500-2
LIGHTING

identified index tab. Catalog cut sheets shall indicate fixture identification, i.e., type
A, D, J, etc., and shall indicate where it will be used.
Information on each fixture shall include:

1.
2.
3.

4
5
6.
7.
8
9.
1

Manufacturer and Catalog Number

Dimensioned Construction Drawing(s)

Standard Catalog "Cut" Sheet modified to show any options/accessories to be
provided

Photometrics of each fixture

Lens/Louver Type for each fixture

Finance Committee - Agenda - 6/7/2017 - P636

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P636

16500-1

SECTION 16500

LIGHTING

PART 1 - GENERAL

1.1

1.2

1.3

DESCRIPTION

A.

Provide complete interior and exterior lighting systems, including fixtures,
standards, poles, hangers, supports, fittings, lamps, wiring, connections and controls,
as indicated in the Contract Documents.

Finance Committee - Agenda - 6/7/2017 - P635

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P635

16050-14
BASIC MATERIALS AND METHODS

4. Provide PVC end caps for all protruding angles, channels, struts, etc. for
personal safety for the entire project installation.
T. Identification of Conduit Systems
1. Provide lamacoid nameplates to mark intrinsically safe conduit systems for all
applicable conduit systems for project.

3.2 TESTS
A. For testing requirements, refer to Section 16950.
B.

END OF SECTION

13089K

Finance Committee - Agenda - 6/7/2017 - P634

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P634

16050-13
BASIC MATERIALS AND METHODS

d. Instrumentation may be grouped with instrumentation

e. Specialty wiring may be grouped with like systems

f. Power wiring at 480V shall not be grouped

g. Fire alarm system wiring shall not be grouped with other systems

Finance Committee - Agenda - 6/7/2017 - P633

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P633

16050-12
BASIC MATERIALS AND METHODS

as manufactured by 3M Co. (pre- insulated "Scotch-Lock") or Ideal ("Wing-

Nuts").

3. For splices and taps, No. 8 and larger, use solderless "Split Bolt" type connector
as manufactured by Anderson, Burndy, Kearney, Thomas & Betts, or
equivalent.

4. Use cast connections, Cadweld or Thermoweld, for ground conductors.

5. Make all splices and connections in accessible boxes and cabinets only.