15750-1

SECTION 15750

HOT WATER COILS

PART 1 - GENERAL

1.1 DESCRIPTION
A. Work Included: Provide and install hot water heating coils of the types, sizes and

B.

capacities shown on the drawings.
Related Work Specified Elsewhere: "HVAC - General" is specified in this division.

1.2 QUALITY ASSURANCE

A.

B.

Verification of Operating Data: Capacities, pressure drops and selection procedures
shall be certified in accordance with ARI Standard 410.

Finance Committee - Agenda - 6/7/2017 - P576

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P576

15732-1

SECTION 15732

CONVERTORS

PART 1 - GENERAL

1.1 DESCRIPTION

A.

B.

Work Included: Furnish and install steam to hot water convertor(s) of type, location,
and capacity as shown on the Drawings.

Related Work Specified Elsewhere: "HVAC - General" is specified in Section 15600;
“Hydronic Heating Systems Piping and Specialties” is specified in Section 15601;
and “Steam Heating Systems Piping and Specialties” is specified in Section 15602.

1.2 QUALITY ASSURANCE

A.

Finance Committee - Agenda - 6/7/2017 - P575

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P575

15671-4
DUCTLESS SPLIT SYSTEM HEAT PUMP UNITS

h. Fan speed controls shall be user-selectable: high, medium, low or
microprocessor controlled automatic operation during all operating
modes.

The unit shall be protected against the following:

i. Indoor coil freeze-up.

j. Indoor coil high temperature protection shall be provided to detect
excessive indoor discharge temperature when unit is in heat pump mode.

5. Filters:
Units shall have filter rack with factory-supplied washable filter.
C. Systems shall be:

Finance Committee - Agenda - 6/7/2017 - P574

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P574

15671-3
DUCTLESS SPLIT SYSTEM HEAT PUMP UNITS

Fans:

a. The unit fan shall be high performance, double inlet, forward curve, direct
drive sirocco fan with a single motor. The fans shall be statically and
dynamically balanced and run on a motor with permanently lubricated
bearings. The indoor fan shall consist of three (3) speeds: Low, Mid, and
Hi and Auto. The fan shall have a selectable Auto fan setting that will
adjust the fan speed based on the difference between controller set-point
and space temperature.

Finance Committee - Agenda - 6/7/2017 - P573

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P573

15671-2
DUCTLESS SPLIT SYSTEM HEAT PUMP UNITS

b. The compressor shall be driven by inverter circuit to control compressor
speed. The compressor speed shall dynamically vary to match the room
load for significantly increasing the efficiency of the system which shall
result in significant energy savings.

c. The unit shall have an accumulator and high pressure safety switch.

d. The compressor shall be mounted to avoid the transmission of vibration.

Outdoor Coil:

Finance Committee - Agenda - 6/7/2017 - P572

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P572

15671-1

SECTION 15671

DUCTLESS SPLIT SYSTEM HEAT PUMP UNITS

PART 1 - GENERAL

1.1 DESCRIPTION
A. Work Included: Furnish and install ductless split system heat pump systems of the
size and capacities as shown on the drawings. Each unit shall include an outdoor
condensing unit, high wall mounted direct expansion fan coil unit, refrigeration
specialties, refrigerant charge and wired remote control.
B. Related Work Specified Elsewhere.
1. "HVAC - General" is specified in this Division.

Finance Committee - Agenda - 6/7/2017 - P571

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P571

15626-2
HVAC SYSTEM PUMPS (IN-LINE CIRCULATORS)

3.2 ADJUSTING
A. Test and run complete heating system under actual working conditions and adjust the
unit to the satisfaction of the Engineer.

END OF SECTION

13089K

Finance Committee - Agenda - 6/7/2017 - P570

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P570

15626-1

SECTION 15626

HVAC SYSTEM PUMPS (IN-LINE CIRCULATORS)

PART 1 - GENERAL

1.1 DESCRIPTION
A. Work Included: Provide and install horizontal inline centrifugal single stage pumps
with the capacities and characteristics as shown on the equipment schedules.
B. Related Work Specified Elsewhere: "HVAC - General" is specified in this Division.

12 QUALITY ASSURANCE

A. Verification of Unit Output: Equipment shall be supplied with manufacturer's
certificate and pump curve for rated performance, horsepower, etc.

Finance Committee - Agenda - 6/7/2017 - P569

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P569

15619-4
GAS FIRED SEPARATED COMBUSTION AIR HANDLING UNITS

3.2 FIELD QUALITY CONTROL

A.

B.
C.

Manufacturer's Field Service: Inspect, test, and adjust components, assemblies, and

equipment installations, including connections. Report results in writing.

Perform tests and inspections and prepare test reports.

Manufacturer's Field Service: Inspect components, assemblies, and equipment

installations, including connections, and to assist in testing. Report results in writing.

Tests and Inspections:

Finance Committee - Agenda - 6/7/2017 - P568

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P568

15619-3
GAS FIRED SEPARATED COMBUSTION AIR HANDLING UNITS

2.4 BLOWER

A. Supply Air: Belt drive motor and blower shall be assembled onto a minimum 14 gauge
galvanized steel platform and must have neoprene vibration isolation devices,
minimum of 1 - 1/8 inches thick.

B. Blower assemblies: Shall be statically and dynamically balanced and designed for
continuous operation at maximum rated fan speed and horsepower.

C. Centrifugal blower housing: Formed and reinforced steel panels to make curved scroll