SECTION 15051

POLYVINYL CHLORIDE (PVC) DRAINAGE PIPE

PART 1 - GENERAL

1.1 DESCRIPTION
A. Work Included: Furnish and install PVC drainage pipe and fittings of the type (s)
and size (s) and in the location (s) shown on the Drawings and as specified herein.
B. Related Work Specified Elsewhere: "Pipe & Pipe Fittings - General" is specified in
this Division.

12 QUALITY ASSURANCE
A. Standards:

1. Pipe and fittings (interior) shall conform to ASTM D-2665S.

2. Pipe and fittings (exterior) shall conform to ASTM D-3034.

3. | Solvent cement shall meet the requirements of ASTM D-2564.
4. Shall have NSF seal of approval.
B. Acceptable Manufacturers:
1. Charlotte Pipe and Foundry Co.
2. Harvel
3. Cabot
4. Or approved equal.
PART 2 - PRODUCTS

2.1 MATERIALS
A. Pipe Outside Buildings:
1. Pipe and Fittings:
a. Virgin Type I, Grade I, or Type I, Grade 2 or as shown on the Drawings.
b. Pipe and Fittings: Gasketed style utilizing twin gasket coupling or single
gasket bell and spigot type.
c. Pipe Lengths: Laying length of 20 feet minimum.
B. Piping Inside Building:
1. Pipe and Fittings:
a. Solvent weld type with drainage type fittings.
b. Type I, Grade I, or Type I, Grade 2 or as shown on the Drawings.
2. Joints:
a. Solvent weld using approved pipe manufacturer's solvent.
b. Couplings: Same schedule as pipe.
C. Adaptors: When applicable, provide adaptors for connecting PVC to pipe
constructed from other materials.

PART 3 - PART 3 - EXECUTION
3.1 INSTALLATION
A. Jointing:

13089K

Page Image
Finance Committee - Agenda - 6/7/2017 - P516

Finance Committee - Agenda - 6/7/2017 - P517

By dnadmin on Mon, 11/07/2022 - 10:24
Document Date
Wed, 06/07/2017 - 00:00
Meeting Description
Finance Committee
Document Type
Agenda
Meeting Date
Wed, 06/07/2017 - 00:00
Page Number
517
Image URL
https://nashuameetingsstorage.blob.core.windows.net/nm-docs-pages/fin_a__060720…

15051-2
POLYVINYL CHLORIDE (PVC) DRAINAGE PIPE

1. Clear each pipe length, coupling and fitting of all debris and dirt before
installing.
2. Provide and use coupling pullers for joining the pipe.
3. Shove home each length of pipe against the pipe previously laid and hold
securely in position.
4. Donot pull or cramp joints.
Fabrication:
1. Cutting:
a. Usea hand saw or pipe cutter with blades (not rollers).
b. Examine all cut ends for possible cracks caused by cutting.
2. Connecting:
a. Solvent weld connections as recommended by the manufacturer.
b. Connect pipe and fittings only when temperature is above the minimum
recommended by the manufacturer.
c. Threaded adapters shall be connected only with plastic male into metal
female.

END OF SECTION

13089K

Page Image
Finance Committee - Agenda - 6/7/2017 - P517

Finance Committee - Agenda - 6/7/2017 - P518

By dnadmin on Mon, 11/07/2022 - 10:24
Document Date
Wed, 06/07/2017 - 00:00
Meeting Description
Finance Committee
Document Type
Agenda
Meeting Date
Wed, 06/07/2017 - 00:00
Page Number
518
Image URL
https://nashuameetingsstorage.blob.core.windows.net/nm-docs-pages/fin_a__060720…

PART 1 - GENERAL

1.1 DESCRIPTION

15061-1

SECTION 15061

STEEL PIPE & FITTINGS

A. Work Included: Furnish and install steel pipe and fittings of the type(s) and size(s)
and in the location(s) shown on the Drawings and as specified herein.

B. Related Work Specified Elsewhere (When Applicable): "Pipe and Pipe Fittings -
General" is specified in this Division.

PART 2 - PRODUCTS

2.1 MATERIALS

A. Standard Steel Pipe:
1. Classes and maximum working pressures shall be as specified in ANSI B31.1
and as shown on the Drawings.

2
3
4

. ASTM A-53 carbon steel, welded or seamless.

. Zine coated (galvanized) or black steel as indicated.

. End connections: As shown on the Drawings.

B. Fittings:

1. General Service Screwed: Standard pattern malleable iron with full length

clean cut threads, ANSI B16.3.
2. Special Service Screwed: Class 2,000 or 3,000 forged steel.

3. Welded:
a. ASTM A-234 made from ASTM A-106 Grade B seamless tube.
b. Long-radius elbows.
c. Reducing tees for one size reduction, weld-o-lets or thread-o-lets for
small take-offs.
d. 150 pound series slip-on or weld neck flanges ANSI B-16.5 using carbon

steel, ASTM A-181, grade 1.

4. Unions: 250 pound series malleable iron with brass to iron seats.
5. Corrosion Resistant Fittings:

a.

b.

Welded corrosion resistant steel pipe shall be of fittings fabricated from
the same alloy as the pipe.

Screwed corrosion resistant steel pipe shall use malleable iron or ductile
iron fittings.

PART 3 - EXECUTION

3.1 INSTALLATION
A. Threaded Joints:
1. Ream the ends of threaded pipe to remove all burrs.
2. Cut threads clean with long tapers.
3. Remove all dirt and chips from the inside of the pipe and fittings and from the
threads.

13089K

Page Image
Finance Committee - Agenda - 6/7/2017 - P518

Finance Committee - Agenda - 6/7/2017 - P519

By dnadmin on Mon, 11/07/2022 - 10:24
Document Date
Wed, 06/07/2017 - 00:00
Meeting Description
Finance Committee
Document Type
Agenda
Meeting Date
Wed, 06/07/2017 - 00:00
Page Number
519
Image URL
https://nashuameetingsstorage.blob.core.windows.net/nm-docs-pages/fin_a__060720…

mo

15061-2
STEEL PIPE & FITTINGS

4. Make up joints with an approved pipe joint compound or tape applied to the
male threads only.

5. When connecting pipes to recessed drainage fittings, seat them against the
shoulder of the fittings.

6. | When required to back off joints, entirely disjoint, wipe the threads of both the
pipe and fittings clean, apply new joint compound, and reassemble the
connection.

Welded Connections:

1. All welding shall conform to ANSI B31.1.

2. All welders shall be certified for types and classes of welds being performed.

3. All welds shall be inspected for quality and suitability. Repair or replace all
unsatisfactory welds.

Flanged Joints:

1. Tighten flange bolts so that the gaskets are uniformly compressed and sealed.

2. Do not distort flanges.

3. Leave flange bolts with the ends projecting 1/8 inch to 3/8 inch beyond the
faces of the nuts after tightening.

4. Gasket material shall be compatible with pipeline fluid.

Cutting: Cut pipe from measurements taken at the site; not from the Drawings.

To permit convenient disassembly for alterations and repairs, install unions or

flanges where shown on the Drawings and:

1. Inlong runs of piping,

In bypasses around equipment,

In connections to traps, tanks, pumps, and other equipment,

Between shutoff valves, and

In other locations as directed by the Engineer, and as indicated on the

Drawings.

wewWN

END OF SECTION

13089K

Page Image
Finance Committee - Agenda - 6/7/2017 - P519

Finance Committee - Agenda - 6/7/2017 - P520

By dnadmin on Mon, 11/07/2022 - 10:24
Document Date
Wed, 06/07/2017 - 00:00
Meeting Description
Finance Committee
Document Type
Agenda
Meeting Date
Wed, 06/07/2017 - 00:00
Page Number
520
Image URL
https://nashuameetingsstorage.blob.core.windows.net/nm-docs-pages/fin_a__060720…

15063-1

SECTION 15063

COPPER PIPE & FITTINGS
(INTERIOR APPLICATIONS)

PART 1 - GENERAL

1.1 DESCRIPTION
A. Work Included: Furnish and install copper pipe and fittings of the type(s) and
size(s) and in the location(s) shown on the Drawings and as specified herein.
B. Related Work Specified Elsewhere:
1. Pipe & Pipe Fittings - General is specified in this Division.

1.2 QUALITY ASSURANCE
A. Pipe: Seamless copper water tube, ASTM B88 (pressure) and ASTM B-306
atmospheric.

PART 2 - PRODUCTS

2.1 MATERIALS
A. Pipe Use (When Applicable):
1. Heating hot water.
a. TypeL or K, hard temper.
B. Fittings:
1. Wrought copper and bronze solder joint pressure fittings: ANSI B16.22.
2. Cast bronze solder joint pressure fittings: ANSI B16.18.
3. Cast bronze solder joint drainage fittings: ANSI B16.23.
4. Cast bronze fittings for flared copper tubes: ANSI B16.26.
C. Solder and Flux:
1. Solid string or wire solder, 95 percent tin, 5% antimony on all pressure piping
and potable water.
Silver solder, 45% brazing silver alloy (where indicated).
Flux: Non-corrosive paste type as required for type of solder.
Acid core, paste type, or solder/flux combinations are not permitted.
Solder or flux containing lead in any form will not be permitted on any
potable water system.

wRwWN

PART 3 - EXECUTION

3.1 INSTALLATION
A. Jointing:
1. Solder Joints:
a. Ream or file pipe to remove burrs.

b. Clean and polish contact surfaces of all joints.

c. Apply flux to both male and female ends.

d. Insert ends of tubes into fittings, the full depth of the sockets.

e. Bring the joints to soldering temperature in as short a time as possible.

13089K

Page Image
Finance Committee - Agenda - 6/7/2017 - P520

Finance Committee - Agenda - 6/7/2017 - P521

By dnadmin on Mon, 11/07/2022 - 10:24
Document Date
Wed, 06/07/2017 - 00:00
Meeting Description
Finance Committee
Document Type
Agenda
Meeting Date
Wed, 06/07/2017 - 00:00
Page Number
521
Image URL
https://nashuameetingsstorage.blob.core.windows.net/nm-docs-pages/fin_a__060720…

15063-2
COPPER PIPE & FITTINGS
(INTERIOR APPLICATIONS)

f. Form continuous solder beads around the entire circumferences of the

joints.
Bending Pipe:
1. Bend pipe by the method and to the radius to comply with the manufacturer's
recommendation.

2. Bends shall be free of any cracks or buckles.

Support: Support all pipes in accordance with the "Pipe Hangers & Supports"
Section in this Division.

To permit convenient disassembly for alterations and repairs, install unions where
shown on the Drawings and:

1 In long runs of piping,

2. In bypasses around equipment,

3. In connections to traps, tanks, pumps, and other equipment,

4 Between shutoff valves, and

5 In other locations as directed by the Engineer.

Remove all valve internals when soldering into pipelines.

END OF SECTION

13089K

Page Image
Finance Committee - Agenda - 6/7/2017 - P521

Finance Committee - Agenda - 6/7/2017 - P522

By dnadmin on Mon, 11/07/2022 - 10:24
Document Date
Wed, 06/07/2017 - 00:00
Meeting Description
Finance Committee
Document Type
Agenda
Meeting Date
Wed, 06/07/2017 - 00:00
Page Number
522
Image URL
https://nashuameetingsstorage.blob.core.windows.net/nm-docs-pages/fin_a__060720…

PART 1 - GENERAL

1.1 DESCRIPTION

15092-1

SECTION 15092

PIPE SLEEVES & SEALS

A. Work Included: Furnish and install wall sleeves and seals of the type(s) and sizes(s)
and in the location(s) shown on the Drawings and specified herein.
B. Related Work Specified Elsewhere:
1. Firestopping is specified in Section 07270.
2 Sealants are specified in Section 07900.
3. | Plumbing - General is specified in Section 15400.
4. HVAC - General is specified in Section 15600.

12 QUALITY ASSURANCE

A. Provide and install all sleeves of the types specified herein, as shown on the Drawings
and as directed by the Engineer.

B. Provide sleeves that are airtight, gastight or watertight as required.

C. Penetrations through fire rated walls, floors and ceiling shall have proper fire
stopping, as specified in Section 07270.

PART 2 - PRODUCTS

2.1 TYPES AND LOCATIONS

A. Penetrations Through Existing Construction:
1. Interior masonry, drywall, or wood partition - Air to Air:

a.

b.

Cleanly cut brick or block as required. Grout sleeve into place using non-
shrink grout.

Cleanly cut wood frames partitions as required. Set sleeve into position
and secure.

Sleeves to be as required for New Construction - Interior masonry,
drywall, or wood partition - Air to Air.

Holes bored with equipment leaving a smooth hole in masonry walls less
than 1/2 inch larger than the pipe will not require a sleeve, unless otherwise
specified.

Minimum 1/4 inch annular space between cored opening or sleeve and
pipe or insulation.

Firmly pack with oakum and seal both ends with polyurethane sealant, per
Section 07900 for standard penetrations.

Install split cover plates in all finished areas. Both sides of wall if required.
Plates shall be chrome finished, suitably sized to fit pipe in question and
cover opening.

2. Exterior Masonry Walls

13089K

Page Image
Finance Committee - Agenda - 6/7/2017 - P522

Finance Committee - Agenda - 6/7/2017 - P523

By dnadmin on Mon, 11/07/2022 - 10:24
Document Date
Wed, 06/07/2017 - 00:00
Meeting Description
Finance Committee
Document Type
Agenda
Meeting Date
Wed, 06/07/2017 - 00:00
Page Number
523
Image URL
https://nashuameetingsstorage.blob.core.windows.net/nm-docs-pages/fin_a__060720…

3, Con
a.

b.

Cc.

d.
B. Rubber Li

15092-2
PIPE SLEEVES & SEALS

Core drill a smooth hole through all layers of the existing masonry. Hole
shall be sized to facilitate standard rubber link compression seal
installation.
Install rubber link compression seal at each layer of masonry.
Seal each face with polyurethane sealant.
If a clean, smooth hole cannot be achieved, remove the masonry as
required to install Schedule 40 galvanized wall sleeve. Pipe sleeve
thicknesses for sizes larger than 24-inch diameter shall be the standard
0.375-inch thickness. Grout sleeve in place. Install rubber link
compression seal and sealant as noted above.

crete Floor Penetrations - Air to Air:
Same as “Interior Concrete Partitions - Air to Air’, except that sleeve will
not be required.
Stainless steel pipe riser clamp with stainless steel threaded rod embedded
into concrete floor to be installed on topside of penetration to support the
pipe vertically.
Install rubber link compression seal, as shown, covered by self-leveling
sealant (SikaFlex or equivalent).
Refer to details on Process Drawings.

nk Compression Seals:

1. Acceptable Manufacturers:

a.
b.
C.
2. Mul

Link Seal by Thunderline Company
Innerlynx by Advance Products and Systems
Or equivalent.
ti-rubber link type with pressure plates, bolts, nuts and sealing element

providing a leak proof seal.
3. General Service (Model C):

a.

b.
C.
d.

Glass Reinforced Nylon Pressure Plate.
Carbon steel zinc-phosphated nut and bolt.
Sealing element: EPDM rubber.
Temperature Rating: -40°F to 250°F.

PART 3 - EXECUTION

3.1

INSTALLATION
A. Existing Construction:

1. The

location will be reviewed and accepted by the Engineer prior to coring or

cutting hole.
2. For concrete, holes shall be located to avoid the reinforcing steel when possible.
3. Patch all damaged work as required to maintain a neat and clean appearance.

B. Rubber Li

nk Compression Seals: Install as required and in strict accordance with the

manufacturer's instructions and recommendations.

END OF SECTION

13089K

Page Image
Finance Committee - Agenda - 6/7/2017 - P523

Finance Committee - Agenda - 6/7/2017 - P524

By dnadmin on Mon, 11/07/2022 - 10:24
Document Date
Wed, 06/07/2017 - 00:00
Meeting Description
Finance Committee
Document Type
Agenda
Meeting Date
Wed, 06/07/2017 - 00:00
Page Number
524
Image URL
https://nashuameetingsstorage.blob.core.windows.net/nm-docs-pages/fin_a__060720…

15094-1

SECTION 15094

PREFABRICATED PIPE HANGERS, SUPPORTS AND BRACING

PART 1 - GENERAL

1.1

1.2

1.3

1.4

DESCRIPTION

A.

Work Included: Design, furnish and install prefabricated pipe hangers, supports,
and braces to support pipes, maintain the necessary pitch, minimize vibration,
prevent movement, and allow expansion and contraction of the pipes shown on the
Drawings, as specified herein and as referenced. This Specification covers hangers,
supports, and braces for mechanical piping systems including ductile iron, carbon
steel, stainless steel and copper piping.

Hangers for electrical conduit, plumbing piping, HVAC ducts, and other utilities are
found within their respective Specification sections.

RELATED SECTIONS

A. Pipe, pipe fittings and valves are specified in respective sections of Division 15.

REFERENCES

A. This section contains references that are applicable to this Specification Section.
The applicable edition of the indicated references shall be the version that was the
most current at the time of the Advertisement of Bids.

B. Manufacturer’s Standardization Society of the Valve and Fittings Industry (MSS).

1. MSS SP-58 Pipe Hangers and Supports — Materials, Design and Manufacture

2. MSS SP-69 Pipe Hangers and Supports — Selection and Application

3. MSS SP-89 Pipe Hangers and Supports — Fabrication and Installation
Practices

4. MSS SP-90 Guidelines on Terminology for Pipe Hangers and Supports

C. ASTM A123/A123M - Specification for Zinc (Hot-Dip Galvanized) Coatings on
Iron & Steel Products

D. ASTM A153/A153M - Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware

E. ASTM C881/C881M - Specification for Epoxy-Resin-Base Bonding Systems for
Concrete

F. ASCE 7 - Minimum Design Loads for Buildings and Other Structures

G. International Building Code (2009)

DESIGN REQUIREMENTS

A. Contractor shall provide all necessary hangers, supports and braces as needed to
provide a fully functional and adequately supported and restrained system.

B. Prefabricated pipe supports shall be provided for all pipes shown on the Contract
Drawings. Unless otherwise indicated, the terms “pipe support’, “pipe hanger” and
“pipe guide” shall refer to prefabricated pipe supports, hangers, guides, and braces
specified herein.

C. All structural steel pipe support frames and shop fabricated pipe support assemblies

13089K

Page Image
Finance Committee - Agenda - 6/7/2017 - P524

Finance Committee - Agenda - 6/7/2017 - P525

By dnadmin on Mon, 11/07/2022 - 10:24
Document Date
Wed, 06/07/2017 - 00:00
Meeting Description
Finance Committee
Document Type
Agenda
Meeting Date
Wed, 06/07/2017 - 00:00
Page Number
525
Image URL
https://nashuameetingsstorage.blob.core.windows.net/nm-docs-pages/fin_a__060720…

15094-2
PREFABRICATED PIPE HANGERS, SUPPORTS AND BRACING

shown on the Contract Drawings are specified elsewhere and not required as part of

this Specification.

Pipes supports shall be classified as one of the following:

1. Type 1 — Supported from an overhead structural member using overhead
hangers, guides, clevises, rollers, clamps or other means as specified herein.

2. Type 2 - Supported from a structural member below the pipe using guides,
rollers, clamps, saddles or other means as specified herein.

3. Type 3 — Supported from an adjacent wall or other vertical structural member
using brackets with either Type 1 supports or Type 2 supports or other means
as specified herein.

4. Type 4 — Miscellaneous Pipe Hangers, Supports and Braces not specifically
identified above.

5. Additionally, each pipe support shall be classified as one of the following
based on function:

a. Type S - Simple Support
b. Type G - Guide Support
c. Type F - Fixed Support

Where flexible joints or couplings are indicated on the Contract Drawings at

equipment, tanks, etc., the end opposite to the piece of equipment, tank, etc., shall

be rigidly supported, to prevent transfer of system forces to the equipment. No
fixed or restraining supports shall be installed between a flexible joint or coupling
and the piece of equipment.

All pipe and appurtenances connected to the equipment shall be supported in a

manner to prevent any strain or load from being imparted on the equipment or

piping system.

Pipe supports shall be provided to minimize forces through valves, split and sleeve

type couplings, flexible expansion joints and to minimize all pipe forces on

equipment housings. Equipment housings shall not be utilized to support
connecting pipes.

Unless otherwise indicated on the Drawings, maximum hanger and support spacing

shall not exceed the following:

1. Copper Pipe:

a. 1” diameter and smaller — 5 feet
b. 11/4”, 1 1/2” and 2” diameter — 7 feet
c. Greater than 2” diameter — 9 feet
2. Steel and Stainless Steel Pipe:
a. 2” diameter and smaller — 7 feet
b. 2%” -4” diameter — 11 feet

3. The maximum support spacings listed above are based on the specific pipes
being full of liquid without any additional vertical loads or thrusts. The actual
required support spacings may be limited to the hangers selected or the
presence of additional loads.

4. Pipe alignment guides shall not be used as vertical support of the piping.

Wall penetration sleeves (link-seal type or equivalent) shall not be used as

support of the piping.

Contractor shall provide pipe supports at the following locations:

WN

13089K

Page Image
Finance Committee - Agenda - 6/7/2017 - P525

Pagination

  • First page « First
  • Previous page ‹‹
  • …
  • Page 1758
  • Page 1759
  • Page 1760
  • Page 1761
  • Current page 1762
  • Page 1763
  • Page 1764
  • Page 1765
  • Page 1766
  • …
  • Next page ››
  • Last page Last »

Search

Meeting Date
Document Date

Footer menu

  • Contact