16050-7
BASIC MATERIALS AND METHODS
a. Safety switch enclosures for non-hazardous locations painted galvanized
steel for NEMA 12 area and stainless steel for NEMA 4X areas.
b. Switches specified as NEMA 7 & 9 shall be furnished in cast aluminum
enclosures with conduit provisions as specified. Enclosures shall be
provided with a bolted cover and with sealing means for hazardous location
protection. "ON" and "OFF" position identification shall be cast into the
cover, not painted on or applied with an adhesive.
8. Acceptable Manufacturers: Square-D, Cutler-Hammer, General Electric,
Siemens, or approved equal.
1. Enclosures
a. Safety switch enclosures for non-hazardous locations painted galvanized
steel for NEMA 12 area and stainless steel for NEMA 4X areas. Refer to
Drawing E-1 for NEMA classifications.
b. Switches specified as NEMA 7 & 9 shall be furnished in cast aluminum
enclosures with conduit provisions as specified. Enclosures shall be
provided with a bolted cover and with sealing means for hazardous location
protection. "ON" and "OFF" position identification shall be cast into the
cover, not painted on or applied with an adhesive.
2. Acceptable Manufacturers: Square-D, Cutler-Hammer, General Electric,
Siemens, or approved equal.
Link Seal
1. Conduit wall and floor seals for cored holes and sleeved openings shall be Link
Seal, Innerlynx or approved equivalent. Refer to the contract drawings for
additional requirements.
Cable Seals
1. Conduit sealing bushings shall be OZ Gedney Co., Type CSB Series or equal.
Conduit Seals-Offs
1. Provide Class I, Div. 1, Group D and Class 1, Div. 2 seals as required by the
N.E.C. Material shall match the conduit in which being installed.
PART 3 - EXECUTION
3.1 INSTALLATION
A.
Unless otherwise noted, wiring for all systems indicated in the Contract Documents
shall consist of insulated conductors installed in raceways in accordance with the
manufacturer's instructions.
1. Raceways shall be continuous from outlet box to outlet box and from outlet box
to cabinet, junction or pull box. Secure and bond raceways to all boxes and
cabinets such that each system of raceways will be electrically continuous
throughout.
1. Contract drawing E-1 NEMA CLASSIFICATIONS FOR ELECTRICAL
EQUIPMENT AND ENCLOSURES indicates the NEMA ratings of each
location at the facility. Unless otherwise indicated on the Drawings and Conduit
Installation Schedule on E-1 install all wiring in the following applicable
raceway system: Wiring above 600 volts in indoor dry locations (NEMA 1 or