Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH

B. Device Plates

1. Device plates and receptacle cover plates for receptacles and light switches
shall be suitably labeled, identifying the circuit number and the panel
name; for example: RP1-12.

2. Device plates shall be identified on the inside of the plate by circuit
number and panelboard.
C. Control Stations
1. Mount equipment so that sufficient access and working space is provided

for ready and safe operation and maintenance.

Finance Committee - Agenda - 11/15/2017 - P345

By dnadmin on Mon, 11/07/2022 - 10:19
  • Read more about Finance Committee - Agenda - 11/15/2017 - P345

Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH

D. Pushbuttons

4. Switches shall be non-illuminated momentary or maintained type rated for
use at 120 VAC. Switches shall green in color for "START" pushbuttons,
and shall be red in color for "STOP" pushbuttons.

5. Provide compatible nameplate for each pushbutton identifying intended
functions (LE. "STOP", "START", ETC.).

Finance Committee - Agenda - 11/15/2017 - P344

By dnadmin on Mon, 11/07/2022 - 10:19
  • Read more about Finance Committee - Agenda - 11/15/2017 - P344

Project Number: 228730
Issue Date: August 2017

C.

1.

2.

3.

4.

WWTE SCADA Upgrades
Nashua, NH

Allen Bradley Company
Appleton Electric Company
Crouse-Hinds Company

Approved equal

Selector Switches

1.

Finance Committee - Agenda - 11/15/2017 - P343

By dnadmin on Mon, 11/07/2022 - 10:19
  • Read more about Finance Committee - Agenda - 11/15/2017 - P343

Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH

C.

D.

Device Plates

1. Device plates for receptacles shall be stainless steel.
Weatherproof Device Plates

1. Provide weatherproof device plates where indicated and required.

Finance Committee - Agenda - 11/15/2017 - P342

By dnadmin on Mon, 11/07/2022 - 10:19
  • Read more about Finance Committee - Agenda - 11/15/2017 - P342

Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH

1. Convenience receptacles for interior use shall be specification grade,
industrial heavy duty type, 20-ampere, 125-volt ac, 2-pole, 3-wire, back
wiring, metal plaster ears, single, duplex (as indicated) grounded,
conforming to NEMA FB 11, NEMA WD 1 and to the 5-20R
configuration in NEMA WD 6. Receptacles shall be white in color.
Provide waterproof in-use covers where indicated and required.

Finance Committee - Agenda - 11/15/2017 - P341

By dnadmin on Mon, 11/07/2022 - 10:19
  • Read more about Finance Committee - Agenda - 11/15/2017 - P341

Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH

1.03 QUALITY ASSURANCE
A. Reference Standards
1. NATIONAL ELECTRICAL CODE (NEC)
2. | UNDERWRITER'S LABORATORIES, INC. (UL)

3. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
(NEMA) COMPLIANCE

1.04 SUBMITTALS

A. Furnish manufacture’s product data, test reports, and materials certifications in
accordance with the specifications.

PART 2 - PRODUCTS
2.01 FLUSH WIRING DEVICES

A. Wall Switches

Finance Committee - Agenda - 11/15/2017 - P340

By dnadmin on Mon, 11/07/2022 - 10:19
  • Read more about Finance Committee - Agenda - 11/15/2017 - P340

Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH

SECTION 26 27 26

WIRING DEVICES

PART 1 - GENERAL

1.01 DESCRIPTION OF WORK

A. The Contractor shall provide the labor, tools, equipment, and materials necessary
to furnish and install wiring devices in accordance with the plans and as specified
herein.

B. This section includes the following:

1. Flush Wiring Devices
2. Control Relays
3. Motor Control Relays/Contactors
4. Control Stations
1.02 RELATED DOCUMENTS

Finance Committee - Agenda - 11/15/2017 - P339

By dnadmin on Mon, 11/07/2022 - 10:19
  • Read more about Finance Committee - Agenda - 11/15/2017 - P339

Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH

This page intentionally left blank

RACEWAYS, BOXES AND SUPPORTING DEVICES
WOODARD & CURRAN 26 05 34-14

Finance Committee - Agenda - 11/15/2017 - P338

By dnadmin on Mon, 11/07/2022 - 10:19
  • Read more about Finance Committee - Agenda - 11/15/2017 - P338

Project Number: 228730 WWTE SCADA Upgrades

Issue Date: August 2017 Nashua, NH
2. Use explosion proof boxes (NEMA 7) in hazardous areas as designated on

the plans.
3. Use watertight boxes (NEMA 4X) for exterior and wet locations on

outdoor structure where moisture is present.

4. Use corrosion resistant watertight boxes (NEMA 4X) for wet locations and
corrosion filled areas, such as the chemical feed area, and as identified on
the Drawings.

END OF SECTION

Finance Committee - Agenda - 11/15/2017 - P337

By dnadmin on Mon, 11/07/2022 - 10:19
  • Read more about Finance Committee - Agenda - 11/15/2017 - P337

Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH

F.

Support individual horizontal raceways by separate pipe hangers. Spring steel
fasteners may be used in lieu of hangers only for 1 1/2 inch and smaller raceways
serving lighting and receptacle branch circuits above suspended ceilings only. For
hanger rods with spring steel fasteners, use 1/4 inch diameter or larger threaded
steel. Use spring steel fasteners that are specifically designed for supporting
single conduits or tubing.