16500-2
LIGHTING

identified index tab. Catalog cut sheets shall indicate fixture identification, i.e., type
A, D, J, etc., and shall indicate where it will be used.
Information on each fixture shall include:

1.
2.
3.

4
5
6.
7.
8
9.
1

Manufacturer and Catalog Number

Dimensioned Construction Drawing(s)

Standard Catalog "Cut" Sheet modified to show any options/accessories to be
provided

Photometrics of each fixture

Lens/Louver Type for each fixture

Finance Committee - Agenda - 6/7/2017 - P636

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P636

16500-1

SECTION 16500

LIGHTING

PART 1 - GENERAL

1.1

1.2

1.3

DESCRIPTION

A.

Provide complete interior and exterior lighting systems, including fixtures,
standards, poles, hangers, supports, fittings, lamps, wiring, connections and controls,
as indicated in the Contract Documents.

Finance Committee - Agenda - 6/7/2017 - P635

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P635

16050-14
BASIC MATERIALS AND METHODS

4. Provide PVC end caps for all protruding angles, channels, struts, etc. for
personal safety for the entire project installation.
T. Identification of Conduit Systems
1. Provide lamacoid nameplates to mark intrinsically safe conduit systems for all
applicable conduit systems for project.

3.2 TESTS
A. For testing requirements, refer to Section 16950.
B.

END OF SECTION

13089K

Finance Committee - Agenda - 6/7/2017 - P634

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P634

16050-13
BASIC MATERIALS AND METHODS

d. Instrumentation may be grouped with instrumentation

e. Specialty wiring may be grouped with like systems

f. Power wiring at 480V shall not be grouped

g. Fire alarm system wiring shall not be grouped with other systems

Finance Committee - Agenda - 6/7/2017 - P633

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P633

16050-12
BASIC MATERIALS AND METHODS

as manufactured by 3M Co. (pre- insulated "Scotch-Lock") or Ideal ("Wing-

Nuts").

3. For splices and taps, No. 8 and larger, use solderless "Split Bolt" type connector
as manufactured by Anderson, Burndy, Kearney, Thomas & Betts, or
equivalent.

4. Use cast connections, Cadweld or Thermoweld, for ground conductors.

5. Make all splices and connections in accessible boxes and cabinets only.

Finance Committee - Agenda - 6/7/2017 - P632

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P632

16050-11
BASIC MATERIALS AND METHODS

Installation of Bushings and Grounding Bushings

1. Provide grounding type insulated bushings on all power conduits regardless of
size.

2. Provide grounding type insulated bushings on all control conduit sizes and
signal conduit sizes one and one-quarter inch (I-1/4") trade size and larger.

3. Provide standard bushings for conduits one inch (I") and smaller unless
otherwise stated.

Finance Committee - Agenda - 6/7/2017 - P631

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P631

16050-10
BASIC MATERIALS AND METHODS

approval for splicing prior to installation of feeder(s). Refer to Splicing
Methods listed below.

Do not pull conductors into raceways until raceway system, including all
outlets, cabinets, bushings and fittings, is completed. Verify that all work of
other trades which may cause conductor damage is completed. Use only
ULL. approved cable lubricants when necessary. Do not use mechanical means
to pull conductors No. 8 or smaller.

Finance Committee - Agenda - 6/7/2017 - P630

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P630

8.

16050-9
BASIC MATERIALS AND METHODS

i. | Used for whips for concealed lights above hung ceiling limited to 3'
in length.

ii. Within studded concealed wood frame walls for receptacles and light
switching.

All signal wiring shall be installed in rigid galvanized steel or PVC coated rigid
galvanized steel conduit.

C. General Raceways Installation Requirements:

1.

ao

10.

11.

12.

13.

14.

Finance Committee - Agenda - 6/7/2017 - P629

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P629

16050-8
BASIC MATERIALS AND METHODS

12) Heavywall aluminum conduit. Galvanized heavy duty rigid steel conduit as

approved by the Engineer.

Wiring 600 volts or less in dry concealed locations [hung above ceilings, attic

areas, or within CMU block walls] (NEMA 1 or 12): Galvanized electrical

metallic tubing (for raceway sizes up to and including 2" trade size) or
galvanized rigid heavy wall steel conduit.

Wiring 600 volts or less in dry exposed indoor locations (NEMA 1 or 12): Rigid

Finance Committee - Agenda - 6/7/2017 - P628

By dnadmin on Mon, 11/07/2022 - 10:24
  • Read more about Finance Committee - Agenda - 6/7/2017 - P628

16050-7
BASIC MATERIALS AND METHODS

a. Safety switch enclosures for non-hazardous locations painted galvanized
steel for NEMA 12 area and stainless steel for NEMA 4X areas.

b. Switches specified as NEMA 7 & 9 shall be furnished in cast aluminum
enclosures with conduit provisions as specified. Enclosures shall be
provided with a bolted cover and with sealing means for hazardous location
protection. "ON" and "OFF" position identification shall be cast into the
cover, not painted on or applied with an adhesive.