AUTOMATIC TEMPERATURE CONTROL (ELECTRIC)
G. Circulating Pump (GCP-1)
1. |The pump shall be energized and operate continuously when either GSF-1 is
energized and the outside air temperature is less than 50°F (adj.).
H. Heat exchanger (CHX-1 & GHX-1)
1. |The associated steam control valve shall open as necessary to maintain a heating
leaving water temperature in accordance with the following temperature