Specification 02560 - Landfill Gas Extraction Wells
January 2021
Page 2 of 4
3066.21
Aggregate shall be washed, and uniformly blended according to the particle
size distribution requirements shown below.
Sieve Size Percent Passing by Weight
2-inch 100
1%-inch 90 - 100
1-inch 30 - 40
%4-inch 10-15
¥Y-inch 0-5
¥s-inch 0-5
2.2 BENTONITE SEAL
A. Bentonite seals shall be installed where shown on the Drawings using a hydrated
bentonite slurry mix poured into place.
2.3 SAND/GRAVEL FILTER
A. Sand/gravel filter shall conform to the following particle size distribution.
Sieve Size Percent Passing by Weight
1%-inch 100
No. 4 70 - 100
No. 40 30 - 80
No. 200 0-15
2.4 PVC PIPE
A. Refer to Specification Section 15212.
2.9 WELLHEAD
A. Wellheads shall be 2-inch QED Precision Quick-Change™ Orifice Plate Wellhead,
or equivalent approved by ENGINEER. The wellhead components are indicated
on the Drawings.
B. Wellhead and flow measurement tube shall be compatible with the
CES/LANDTEC GEM-2000™ and GEM-5000™ Landfill Gas Monitors.
PART 3 - EXECUTION
3.1
DRILLING
A. OWNER or ENGINEER shall observe all drilling operations.
SANBORN HEAD