Digital outputs
Relay outputs
Assigned switching and protective elements

Power Wiring
Main choke

150 % overload (CT/Iy, at 50 °C)

Note regarding mains choke

Motor feeder
motor choke
150 % overload (CT/Iy, at 50 °C)
110 % overload (VT/I,, at 40 °C)
Sine filter
150 % overload (CT/Iy, at 50 °C)

110 % overload (VT/I,, at 40 °C)

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation
Heat dissipation per pole, current-dependent
Equipment heat dissipation, current-dependent
Static heat dissipation, non-current-dependent
Heat dissipation capacity

Operating ambient temperature min.

Operating ambient temperature max.

IEC/EN 61489 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance

10.2.3.1 Verification of thermal stability of enclosures

10.2.3.2 Verification of resistance of insulating materials to normal heat

10.2.3.3 Verification of resistance of insulating materials to abnormal heat

and fire due to internal electric effects
10.2.4 Resistance to ultra-violet (UV) radiation
10.2.5 Lifting
10.2.6 Mechanical impact
10.2.7 Inscriptions
10.3 Degree of protection of ASSEMBLIES
10.4 Clearances and creepage distances
10.5 Protection against electric shock
10.6 Incorporation of switching devices and components
10.7 Internal electrical circuits and connections
10.8 Connections for external conductors
10.9 Insulation properties
10.9.2 Power-frequency electric strength
10.9.3 Impulse withstand voltage
10.9.4 Testing of enclosures made of insulating material

10.10 Temperature rise

10.11 Short-circuit rating

10.12 Electromagnetic compatibility

10.13 Mechanical function

06/15/2021

ln A
Pyid Ww
Pyid Ww
Pus WwW
Puiss WwW
°C
°C

Eaton 125670 ED2021 V80.0 EN

1, parameterizable, 48 V DC/50 mA
2, parameterizable, N/O, 8 A (24 V DC) /8 A (250 V AC) /0,4A (125 VDC)

DX-LN3-300

Mains choke recommended only if the power quality is poor. Current harmonics
(THD) are attenuated by internal DC link chokes.

DX-LM3-260

DX-LM3-303

DX-SIN3-250

DX-SIN3-440

245

3300

50

Operation (with 150 % overload)

Meets the product standard's requirements.
Meets the product standard's requirements.
Meets the product standard's requirements.

Meets the product standard's requirements.

Meets the product standard's requirements.

Does not apply, since the entire switchgear needs to be evaluated.
Does not apply, since the entire switchgear needs to be evaluated.
Meets the product standard's requirements.

Does not apply, since the entire switchgear needs to be evaluated.
Meets the product standard's requirements.

Does not apply, since the entire switchgear needs to be evaluated.
Does not apply, since the entire switchgear needs to be evaluated.
Is the panel builder's responsibility.

Is the panel builder's responsibility.

Is the panel builder's responsibility.
Is the panel builder's responsibility.
Is the panel builder's responsibility.

The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.

Is the panel builder's responsibility. The specifications for the switchgear must be
observed.

Is the panel builder's responsibility. The specifications for the switchgear must be
observed.

The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.

3/4