27 — Under Voltage
32 — Directional Power Relay (Reverse Power)
40 — Loss of Field
46 — Negative Sequence
51V — Over Current (Voltage Restrained)
59 — Overvoltage
64S — Stator Ground Detection (59N)
81 — Over / Under Frequency
87G — Generator Differential
3.5 BALANCE OF PLANT
3.5.1 Field Instrumentation
The control system offered as part of this proposal, includes the integration of all new and
existing field instrumentation.
3.5.2 DC Battery System
Included in this offer is a new protection and control battery system, including 103 AH, Lead
Calcium Battery Bank, 2 Tier Rack, Spill Containment, 240 VAC Battery Charger, and fused
isolation disconnect.
3.5.3 Station Service
It is likely that the station service equipment, including lighting, HVAC, hydraulics, etc. will
require some level of attention, with the plant repowering and reconfiguration. As it is
difficult to determine the scope required at this time, the engineering, procurement and
construction activities associated with this equipment is not included as part of this offer.
4. INSTALLATION AND REMOVAL SERVICES
4.1 INSTALLATION SERVICES
At this time, construction and installation services are excluded.
4.2 DEMOLITION & REMOVAL
At this time, demolition and removal services are excluded.