ATTACHMENT 1 TO SECTION 15210
HYDROSTATIC PIPE PRESSURE TEST LOG
Project No.:
| Project Name:
SANBORN | | HEAD Project Location:
Buflding Trust. Engineering Success.
Weather
Contractor: Test No.
Sanborn Head Personnel: Person/Company Performing the Test:
Date of Test: Time of Test: Start: Finish:
Pipe Length: ft. Pipe Diameter: in. Pipe Material: Pipe SDR/Sch.:
Rated Working Pressure: Test Pressure:
Location/designation of pipe tested:
t Pe Pc Amount of
Time Pressure Gauge Pressure Make-Up Water Added
(hours) Reading Dro
(psig) (%) (gal.)
0
1
2
3
4
5
6
Pass Fail Retest? Yes No
Description/location of defects for failed test:
Test Procedure:
Pressurize to 150 percent of rated pressure;
Add make-up water each hour for three hours to maintain pressure;
Test phase begins after the initial three-hour phase;
After one, two or three hours add a measured amount of makeup water to return to the test pressure; and
The amount of makeup water added to return to the test pressure must not exceed the amount in the
makeup water test values table on the back of this sheet.
we wWN PR
Comments:
Signature:
File No. 3066.09 HDPE Pipe, Fittings, and Appurtenances 15210 - 13 of 15 Revised February 2019