4. Pipe to be tested shall be exposed in the trench, except bends, reduced

pressure rated fittings and components, which shall be buried or

restrained. Flange connections shall be visible to check for leaks.

Test pressure shall be 10 psig.

6. Test shall be accepted if the pressure drop over 10 minutes is less than 5
percent of the pressure at the beginning of the test period.

ut

F. Test Report
1. Pressure testing shall be documented using one of the test logs provided
as Attachment 1 and 2 to this Specification depending on the test method
utilized by the CONTRACTOR.
2. CQA Consultant shall record the following information for each test.
Date of test.
Description and identification of piping system tested.
Type of test performed.
Test fluid.
Test pressure.
Results of test.
Type and location of leaks detected.
Corrective action taken to repair leaks.
Results of retesting.
Name of person performing test.

oro moan oe

[END OF SECTION 15210]

P:\3000s\3066.09\Source Files\Type II App\Specifications\ Division 15 Specifications\15210 HDPE.docx

File No. 3066.09 High-Density Polyethylene Pipe 15210 - 12 of 15 Revised February 2019