Otterbine Barebo Inc.

INSPECT AERATOR EQUIPMENT

Immediately report any shipping damage to the carrier that delivered your aerator.

Inspect your aerator and verify the following:
Unit - Check the nameplate located on the housing of the aerator unit to make sure you have received the correct
horsepower and voltage aerator.

Power Control Center - Verify the PCC is compatible with the aerator unit horsepower and voltage. Refer to the electrical
specifications on the nameplate located inside on the door of the PCC.

Power Cable Assembly - Verify the correct cable gauge and length.

For proper warranty consideration return your Otterbine warranty registration card.

ELECTRICALIPCC INSTALLATION

ELECTRICAL INSTALLATION MUST BE PERFORMED BY A QUALIFIED LICENSED ELECTRICIAN AND CONFORM
TO ALL APPLICABLE LOCAL AND NATIONAL CODES

DISCONNECT EQUIPMENT FROM ELECTRICAL SUPPLY BEFORE SERVICING OR PERFORMING MAINTENANCE
Use Only OTTERBINE power cord. Do not splice or repair the cord, replacement is necessary if damage occurs.

The standard Power Control Center includes a fiberglass NEMA 4X enclosure with twenty-four hour timer control in the
auto setting or manual control of the aerator unit, the required motor short circuit, ground fault and overcurrent protection,
surge protection, and personnel GFCI protection (except 460V 60Hz. applications). On 460V units EPD (Equipment
Protection Device) is an optional accessory to provide 5, 10 or 30 mA ground fault protection.

Caution: GFCI Protection is required. If GFCI protection is not used, serious or FATAL electrical shock may
occur.

Attention: GFCI/RCD de protection est nécessaire. Graves ou mortelles choc électrique peut se produire s'il n'est
pas utilisé.

A. Feeder

1. Proper feeder circuit protection in accordance with all applicable local and national codes must be provided to the
power control center.

2. Be certain to properly size feeder conductors to allow for no more than 5% voltage drop for the entire circuit from the
feeder source to the aerator unit. Failure to do so may damage the aerator and void product warranty.

60Hz. Electrical Specifications
HP Volts Phase | Full Load Amps

1 115 1 15.5
1 208/230 1 8.3/7.5
2 208/230 1 13.7/12.4
3 208/230 4 15.51/14
3 208/230 3 9.7/8.6
3 380 3 4.6
3 460 3 4.3
5 | 230 Only 1 23
5 208/230 3 15.1/13.4
5 380 3 7.6
5 460 3 7.2
5 575 3 5.5

B. PCC Location

1. The power control center should be mounted where easily visible from the shoreline where the aerator is located.
Important: The power control center shall not be accessible from the water.

Important: Le Centre de Contréle de la puissance ne doit pas étre accessible a partir de l'eau

www.otterbine.com
1-800-AER8TER 75-0073 Rev 08 60Hz Concept 3 5