Component: 2 ila) Adare’ Bia)

Direct Expansion Coil
Coll tiedei Total Capacity Sensible Capacity Number of Coils Sumber of Rows

Shipping Section: 1

Fins per inch Tube Diameter

Tube Spacing
(Face x Row)
5€J0706C 228871 Btu/hr 150859 Btu/hr 1 6 7 0.625 in 1.50 in x 1.299 in
Air Volume Air Temperature Coil Air Finned Finned Face Area Face
Entering Leaving Pressure Height Length Velocity
Dry Bulb Wet Bulb Dry Bulb Wet Buib Drop
5545 cfm 80.0 °F 67,0°F S5.1°F 53.5 °F 0.93 inWe 33 in 53 in 12.15 ft? 457 ft/min
Fluid Sub-Cooled Refrigerant Suction Vapor Design Saturated Total Refrigerant
Suction Temp. Refrigerant Liquid Temp. Superheat Condensing Temp. Weight
Temp, at Coll Outiet
44.0°F R410a 110.0°F 8.0°F 110.0 °F 38.0 Ib
Connection [Data Per Coll] Win. Fin Surface Min. Tube Wall
Type Uquid [Qty-Size] Suction [Qty - Size] Location Material Temp. Surface Temp.
OD Sweat 2-0.88 in 2-1.63 in Drive side Copper tube 32.0°F 32.0°F
Material Drain Pan Drain Side
Fin Tube Header Case
Aluminum .0075 in Copper .020 in Copper Galv. steel Stainless steel Drive side
Component performance shawn is based on the component air volume shown.
Static pressure shown is based on the component air volume shown.
AHRI 410 Certification
Coil is NOT certified by AHRI
* Reheat Hot Water Coil
Cail Model Total Capacity Number of Coils Number of Rows Fins per inch Tube Diameter Tube Spacing
(Face x Row)
5WQ1201C 227585 Btu/hr 1 1 12 0.625 in 1.50 in x 1.299 in
Air Volume Air Temperature Coil Air Pressure Finned Height Finaed Length Face Area Face Velocity
Entering Leaving Crop
Ory Bulb Ory Bulb
5545 cfm $3.0 °F 90.5 °F 0.18 inwe 33 in 50in 11.46 484 ft/min
Water Fiow Rate Pressure Drop Velocity Volume Weight
Entering Leaving
180.0 "F 139.4 °F 11.20 gpm 2.10 ftHd 2.00 ft/s 3.0 gal 26.00 ib
Connection [Data Per Coil] Min. Fin Surface Min. Tube Wall Fouling Factor
Type Size Location Wiaterial Temp. Surface Temp.
Threaded 1.50 in Drive side Carbon steel 139.4 °F 139.4 °F 0.000
Rateriat
Fin Tube Header Case
Aluminum .0075 in Copper .020 in Copper Galv. steel
Component performance shown is based on the component air volume shown.
Static pressure shown is based on the component air volume shown.
_ AHR) 410 Certification

ee

Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Aiz-Heating Coils Certification Program
which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the
Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org

Type 63 Hz

125 Hz 250 Hz $00 Hz 1000 Hz 2000 Kz 4000 Hz 8000 Hz
Radiated: 64 54 48 41 39 41 46 51
Unit Discharge: 64 54 48 41 39 41 46 51
Unit Return: 64 54 48 41 39 41 46 51
Job Number: J4FOS3 Page Prepared Data: 2/20/2019
Job idame: 21900368 Nashua Fire Station - 11 of 18

www.DaikinApplied.com