Technical Data Sheet for HVAC-1 Repiacemenit #2
Job Information Technical Data Sheet wT
Job Name 21900368 Nashua Fire Station - Lake Street F SQ
Date February 20 2019 "
Submitted By DA
Software Version 11.75
Unit Tag HVAC-1 Replacement #2
Unit Overview
LY foye Ca reel oy-1g
CACOLIGBAM
Air Volume
Cotte)
5545
Static Pressure External Dimensions
Secge Total
Tan fel inWe
: a2* 66"
2.00 | 0,00 52
*Not including base roils, coil connectors, drain connectars and control boxes.
Model Number:
Approval:
Outer Panel:
Uner:
insulation:
Unit Configuration:
Base:
Altitude:
CACO13GBAM
ETL Listed / ETL Listed to Canadian Safety Standards (ETL Label / ETLc Label}
24 gauge G90 Galvanized Steel (unpainted)
24 gauge Galvanized Steel (unless noted per section)
R-13 Injected Foam
inline horizontal Drive (Handling) Location: Right
None Wall Thickness: 2 in
Ott Parts Warranty: Standard One Year
Nt Box pets Shipping Section: 1
Damper Rated CFM Air Pressure Quantity
Size (length x width) Location Type Drop
Overall Opening
Outside Air 20 in x 62 in 16in x 52 in End uiese om 5545 cfm 0.07 insWg 1
It
Retum Air §— 20inx62in —-16in x S2in Top : _ Low 5545 cfm 1
Fitter Data
Type Efficiency Face Velocity Face Area Air Volume Fitter Loading
Pleated MERV 8 420 ft/min 13.2 f? 5545 cfm Side
Air Pressure Drop Number of Filters Height Uvidth Depth
Clean Air Mean Air Dirty Air
; ; , 3 24 in 20 in 2in
0.18 inwc 0.59 inwc 1.00 inwe 2 12in 24 in Din
Door
Location Width Opening
Drive side 24 in Outward
Job Number: J4FO53 Page Prepared Date: 2/20/2019
Job Name: 21900368 Nashua Fire Station - 10 of 18 www.DaikinApplied.com