Technicai Data Sheet for HVAC-1 Replacement #1

Combination Coil Length: 24 in Shipping Section: 1

Direct Expansion Coil
Coll Model Total Capacity Sencthle Capacity NumberofCels Number of Rows Fins per inch Tube Diameter Tube Spacing
(Face x Row)
SEJO806C 197017 Btu/hr §=—- 130883 Btu/hr i 6 8 0.625 in 1.50 in x 1.299 in
Air Volume Air Temperature Coil Air Finned Finned Face Area Face
Entering Leaving Pressure Height Length Velocity
Dry Bulb Wet Bulb Dry Bulb Wet Bulb Drop
4805 cfm 80.0 °F 67.0 °F 55.1 °F 53.6 °F 1.26 inWe 27 in 49 in 9.19 fe? 523 ft/min
Fluid Sub-Cooled Refrigerant Suction Vapor Design Saturated Total Refrigerant
Suction Temp. Refrigerant Liquid Temp. Superheat Condensing Temp. Weight
Temp. at Coll Outlet
44.0°F R410a 110.0 °F 8.0°F 110.0 °F 29.0 tb
Connection [Data Per Coil] Min. Fin Surface Min. Tube Wall
Type Liquid [Qty- Size] Suction [Qty - Size] Location Material Temp. Surface Temp.
OD Sweat 2-0.88 in 2-1.63 in Drive side Copper tube 32.0 °F 32.0°F
Material Drain Pan Brain Side
Fin Tube Header Case
Aluminum .0075 in Copper .020 in Copper Galv. steel Stainless steel Drive side
Component performance shown is based on the component air volume shown.
Static pressure shown is based on the component air volume shown.
AHR 410 Certification
Coil is NOT certified by AHRI
Reheat Hot Water Coil
Coil Model Total Capacity Number of Coils Number of Rows Fins per inch Tube Diameter Tube Spacing
(Face x Row)
5WQ1401C 200744 Btu/hr 1 1 14 0.625 in 1.50 in x 1.299 in
Air Volume Air Temperature Coil Air Pressure Finned Height Finned Lenzth Face Area Face Velocity
Entering Leaving Drop
Dry Bulb Dry Bulb
4805 cfm 53.0 °F 91.2°F 0.25 inwe 27 in 46 in 8.63 fe? 557 ft/min
Water Flow Rate Pressure Drop Velocity Yolume Weight
Entering Leaving
180.0 °F 138.7 °F 9.70 gpm 2.00 ftHd 2.10 ft/s 2.0 gal 21.00 Ib
Connection [Data Per Coil] Min. Fin Surface Min. Tube Wall Fouling Factor
Type Size Location Material Temp. Surface Temp.
Threaded 1.50 in Drive side Carbon steel 138.7 °F 138.7 *F 0.000
Material
Fin Tube Header Case
Aluminum .0075 in Copper .020 in Copper Galv. steel

Component performance shown is based on the component air volume shown.
Static pressure shown is based on the component air volume shown.
AHRI 410 Certification
Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program
which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the
Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org

Pvwee Bol ay a ge

Type 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz od
Radiated: 64 54 48 41 39 41 46 $i
Unit Discharge: 64 54 48 41 39 41 46 51
Unit Return: 64 54 48 41 39 41 46 51
Job Number: J4FO53 Page Prepared Date: 2/20/2019

Job Name: 21900368 Nashua Fire Station - 4 of 18 www.DaikinApplied.com