Technical Data Sheet for HYAC-1 Replacement #1
Jobinformation
job Name
Date
Submitted By
Software Version
Unit Tag
ues
21900368 Nashua Fire Station - Lake Street
February 20 2019
DA
11.75
HVAC-1 Replacement #1
Unit Overview
Air Volume
Static Pressure Per epee
Scary) Total
inWe hia
2.60 0,00 36° 62*
Model Number
Cciae]
nN
CACOLOGBAM | 4805
*Not including base rails, coil connectors, drain connectors and control boxes.
Model Number: CACO10GBAM
Approval: ETL Listed / ETL Listed to Canadian Safety Standards (ETL Label / ETLc Label)
Guter Panel: 24 gauge G90 Galvanized Steel (unpainted)
Liner: 24 gauge Galvanized Steel (unless noted per section)
Insulation: R-13 Injected Foam
Unit Configuration: — Inline horizontal Drive (Handling) Location: Right
Base: None Wall Thickness: 2 in
Altitude: Of Parts Warranty: Standard One Year
Portion Damper Rated CFM Alr Pressure Quantity
Size (length x width) Location Type Drop
Cverall Opening
; ; UltraSeal Low .
Outside Air = 20 in x 5B in 16 in x 48 in End Leak 4805 cfm 0.06 inswe 1
RetumAlr —20inx58in 16 in x 48in Top Uierasea! Low 4805 cfm 1
Filter Data
Type Efficiency Face Velocity Face Area Alr Volume Filter Loading
Pleated MERV 8 $09 ft/min 9.4 f? 4805 cfm Side
Air Pressure Drop Number of Filters Height Width Depth
Gean Air Mean Alr Dirty Alr
2 24 in 24 in 2in
0.24 inWc 0.62 inWc 1.00 inwe 1 24 in 42 in Zin
Door
Location Width Opening
Drive side 24 in Outward
Job Number: J4F053 Page Prepared Date: 2/20/2019
Job Name: 21900368 Nashua Fire Station - 3 of 18 www.DaikinApplied.com