Cooling
Radiator Systam _ 60 Hz 50 Hz
Ambient temperature, °C (°F) 45 (113)
Engine jacket water capacity, L (gal.) 2.65 (0.7)
Aladiator system capacity, Including
engine, L (gal.) t3.2 (3.5)
Water pump type Centrifugal
Fan diameter, mm (in.)
Fan power requirements (powered by
engine battery charging alternator)
Operation Requirements
qty. 3 @ 406 (16)
12VC¢, 18 amps each
Alr Requirements 60 Hz 50 Hz
Radiator-cooled cooling air,
m3jmin. (scfm) + 51 (1800) 51 (1800)
Combustion alr, m3/mm. (cfm) 1.6 (57) 1.3 (45)
Air over engine, m3/min. (cfm) 25 (900) 25 (900)
{ Air density = 1.20 kgim? (0.075 thm/ft?)
Fuel Consumptiont
Natural Gas, m/hr. (cfh) at % load 60 Hz 50 Hz
100% 12,0 (424) 10.0 (353)
75% 9.8 (345) 8.2 (289)
50% 7.6 {268} 6,5 (222)
25% 5.5 (196} 4.5 (159)
Exercise 3.4 (121} 28 (89)
LP Gas, mhr. (cfh} at % load 60 Hz 50 Hz
100% 4.7 (166) 3.9 (138)
75% 3.7 (132) 3.0 (108)
50% 2.8 (100) 2,3 (81)
25% 1.9 (69) 1.6 (56)
Exercise 1.2 (41) 1.0 (35)
+ Nominal Fuel Rating: Natural gas, 37 MJ/m> (1000 Btu/ft?}
LP Vapor, 93 Mm? (2500 Btu/ft3)
LP vapor conversion factors:
8.58 ft.3 = 1 Ib.
0.535 m? = 1 kg.
96,39 ft. = 1 gal.
Sound Enclosure Features
® Sound-attenuating enclosure uses acoustic insulation that
meets UL 94 HF1 flammability classification and repels
moisture absorption.
e Internally mounted critical silencer.
e Skid-mounted, aluminum construction with two removable
access panels.
e Fade-, scratch-, and corrosion-resistant Kohler® cashmere
powder-baked finish.
Sound Data
Application Data
RDC2 Controller
The RDC2 controller provides integrated control for the
generator set, Kohler® Model RXT transfer switch,
programmable interface module {PIM}, and load management.
The RDC2 controller's 2-line LCD screen displays status
messages and system settings that are clear and easy to read,
even in direct sunlight or low light.
RDC2 Controller Features
e Membrane keypad
° OFF, AUTO, and RUIN push buttons
o Select and arrow buttons for access to system
configuration and adjustment menus
e LED indicators for OFF, AUTO, and RUN modes
e LED indicators for utility power and generatar set source
availability and ATS position (Model RXT transier switch
required)
e LCD screen
© Two lines x 16 characters per line
© Backlit display with adjustable contrast for excellent
visibility in all lighting conditions
e Scrolling system status display
Generator set status
Voltage and frequency
Engine temperature
Oil pressure
Battery vottage
& Engine runtime hours
« Date and time displays
e Smart engine cooldown senses engine temperature
e Digital isochronous governor to maintain steady-state speed
at all loads
e Digital voltage regulation: + 1.0% RMS no-load to full-load
e Automatic start with programmed cranking cycle
e Programmable exerciser can be set to start automatically on
any future day and time, and to run every week or every two
eod
e
Model 30RCL & point logarithmic average sound levels are
54 dB(A) during weekly engine exercise and 61 dB(A) during
fullespeed generator diagnostics and normal operation. For
comparison to competitor ratings, the lowest point sound levels
are 52 dB(A) and 60 dB(A) respectively. *
All sound levels are measured at 7 meters with no load.
* Lowest of 8 points measured around the generator. Sound levels at other points
araund generator may vary depending on installation paramaters.
weeks
Exercise modes
« Unloaded exercise with complete system diagnostics
& Unloaded full-speed exercise
* Loaded ful-speed exercise {Model AXT ATS required)
Front-access mini USB connector for SiteTech™ connection
Integral Ethemet connector for Kohler® OnCue* Plus
Built-in 2.5 amp battery charger
Remote two-wire start/stop capability for optional connection
of a Model RDT transfer switch
See additional controller features on the next page.
4-229 (ORCL) 4/16