November 3, 2016

Nashua Police Department
One Panther Drive
Nashua NH 03061

Dear Jerry Pilon,

We are pleased to submit the following quotation for the Fire Alarm Control Panel replacement. The
components for the existing system are no longer available from the manufacturer. In the event of a
system failure we may not be able to repair the system.

Scope: -Replace existing fire alarm control panel with a new EST3 addressable FACP
-Replace all existing initiation devices with new addressable
-Replace existing annunciator with new LCD annunciator
Existing hom and strobes to remein
-Add relays for elevator recall interface
-Add monitor modules for sprinklers flow and tampers
-Test the system with Nashua Fire Department
-Pravide 3yr Warranty on the new material provided.

Equipment: (1) 3-CABI4B — wall box for 2 3-CHAS7
(1) 3-CAB14DR — red door package
(1) 3-CHAS7 ~ mounting chassis
(1) 3-CPU3 ~ main control for FACP or network node
(1) 3-LCD — main display for FACP or network node
(1) 3-12/SIRY — switch displays
(1) 3-PPS/M ~ primary power supply with monitor module
(2) 3-SSDCi ~ single analog/addressable signature loop
(1) 3-1DC8/4 — class B conventional input/output module
(1) 3-RS485A - class A network comm. module
(2) 3-XFP ~ blank plate
(4) 3-LRMF = local rail filler
(1) 3-LCDANN -— LCD only ann
(1) RLCM/S ~ flush wall box for 3-LCDANN
(1) XL8 — Spaceage cabinet
(2) BPS-10A - 10 amp signal panel
(76) SIGA2-PS — smoke detectors
(48) SIG2-HFS ~ fixed temp heat detectors