4.

16010-5
ELECTRICAL - GENERAL

Secure and pay for all permits, fees and licenses necessary for the proper
execution of the work under DIVISION 16.

Tests and Procedures Prior To Start-up:

Refer to Section 16950 - Testing Electrical Systems and start-up for testing and
scheduling requirements.

Demonstration of Complete Electrical Systems:

1.

2.
Iden
1.

The Owner will assume no liability or responsibility for any portions of the
installation under this Contract until they are demonstrated and accepted in
writing. Final demonstrations shall be made only after the Engineer is satisfied
that the work has been completed in accordance with the intent of the Contract
Documents.

Refer to Section 16950 for additional requirements.

tification:

All distribution equipment (switchboards, motor control centers, distribution

panelboards, transformers, transfer switches, disconnects, starters, control

panels, control stations, etc.) shall have an engraved lamacoid tag, permanently

mounted adjacent to the manufacturer's nameplate, indicating the equipment's

designation (as called out on the Drawings) and identification number per the

Contract Documents.

All switchboard and distribution panel overcurrent devices, motor control

center devices, individually mounted motor controllers, disconnect switches,

control devices, etc., shall be provided with permanently attached engraved

lamacoid tags indicating the equipment which they serve or control per the

equipment designation and identification number indicated in the Contract

Documents, and in accordance with OSHA requirements.

All branch circuit panelboards shall have, on the inner side of the door, a

permanently attached, engraved lamacoid tag with the identification number of

that panelboard. Provide and mount under plastic, in the directory frame of

each panelboard, a neatly typewritten directory identifying the branch circuit

overcurrent devices and the circuits, devices and areas which they serve.

All individually mounted panelboards, disconnects, motor controllers, control

stations, etc. shall have a second engraved lamacoid tag below the first one

which identifies from where the equipment is receiving power. This second

label shall be smaller in height.

Nomenclature on these nametags shall be project specific and wherever

possible shall be full and complete. Excess abbreviations will not be allowed.

Power conductors shall be continuously polarized and color coded throughout

using the following scheme:

a. White or gray - All neutral conductors, 208/120V systems

b. White w/tracer of any color but Green - All neutral conductors, 480/277 volt
systems

c. Green - All ground conductors

d. Phase Conductors

208/120V 240/120V 480/277V
Systems Systems Systems
Phase A - Black Phase A - Black/(Red) Phase A - Yellow

13089K