TESTING AND BALANCING HEATING AND VENTILATING SYSTEMS

data (as applicable):
1. Equipment (fan or factory fabricated station unit):
a. Installation Data:
i. Manufacturer and Model.
ii. Size.
iit. Arrangement, Discharge, and Class.
iv. Motor H.P., Voltage, Phase, Cycles and Full Load Amps.
v. _ Location and Local Identification Data.
b. Design Data: Data listed in schedules on the Drawings and in the
Specifications.
c. Fan Recorded (Test) Data:
i. C.F.M.: Discharge CFM and % of OA under minimum conditions.
ii. Static Pressure: S.P. total, S.P. suction and S.P. discharge.
iit. R.P.M.: Fan and motor.
iv. Motor Operating Amps.
v. Motor Operating B.H_P.
vi. Motor Sheave Size and Make.
vii. Fan Sheave Size and Make.
vili. Number of Belts Size and Make.
2. Duct Systems:
a. Duct Air Quantities (Maximum and Minimum) - Main, Submains,
Branches, Outdoor (Outside) Air, Total-Air, and Exhaust:
i. Duct size(s)
it. | Number of Pitot tube (Pressure) Measurements.
iit. Sum of Velocity Measurements (Note: Do not add pressure
measurements).
iv. Average Velocity.
v. Recorded (Test) C.F.M.
vi. Design C.F.M.
b. Individual Air Terminals:
i. Terminal Identification (Supply or Exhaust, Location and Number
designation).
ii. Type, Size, Manufacturer and Catalog Identification.
iit. Applicable Factor for Application, Velocity, Area, etc., and
Designated Area.
iv. Design and Recorded Velocities - F.P.M. (State "core", "inlet",
etc., as applicable). Record data for three readings and average.
v. Design and Recorded Quantities - C.F.M. Record data for three
readings and average.
vi. Deflector Vane or Diffusion Cone Settings.

3.6 WATER SYSTEM DATA
A. Report: Include in the certified report, for each water system, the following data:

1. Pumps:
a. Installation Data:
i. Manufacturer and Model.
ii. Size.

13089K