LOUVERS

PART 2 - PRODUCTS

2.1 MATERIALS
A. Exterior Stationary Louvers:

1. | Equal to Greenheck model EDJ-401.

2. Storm proof, .081 extruded aluminum 6063-T5 blades.

3. Architectural style.

4 6063-T5 extruded structural aluminum frame, 0.100" wall thickness, mitered
corners and caulking slots.

5. Rigid hidden architectural style mullions as required for span, but not greater
than 48" on center. Provide mullions at each section of louver requiring duct
or fan connection.

6. Blade stiffeners.

7. 1/2 inch mesh replaceable aluminum bird screen on interior, insect screen
where shown on the Drawings.
Kynar 500 finish - manufacturer's standard color selected by Engineer.
4 inch width.

0. Provide extended sill.
1. Caulk slots and flange when installed in masonry construction. Provide
nailing flange when installed in wood frame construction.

PART 3 - EXECUTION

3.1 INSTALLATION
A. Install as required using manufacturer's instructions and recommendations and as
shown on the Drawings.
B. Caulk all openings as required in Division 7 and as shown on the Drawings.
C. Isolate metal to metal contact between aluminum louver frames and steel damper
frames or ductwork with suitable paint.

3.2 CLEANING AND ADJUSTING
A. Clean all louvers and dampers of grease, tar and dirt to the satisfaction of the
Engineer.
B. Adjust all louvers to the satisfaction of the Engineer.

END OF SECTION

13089K