Submit Shop Drawings per SECTION 16010.
Submit test results on all feeder conductors and heat trace cables as specified in

vo

16050-3
BASIC MATERIALS AND METHODS

Control Devices and Equipment

Motor Starters

Safety Disconnect Switches

Lighting Fixtures

Lighting flexible hangers

Conduit and wall and floor link seal fittings
Conduit cable sealing fittings

SECTION 16950.

PART 2 - PRODUCTS

2.1 MATERIALS
A. Conduit, Raceway and Tubing

1.

Rigid Heavy Wall Steel Conduit (RSC or RGS) shall be constructed of hot
dipped galvanized or electro-galvanized steel. Acceptable Manufacturers:
Allied, Wheatland, or equivalent.

Electrical Metallic Tubing (EMT) shall be constructed of electro-galvanized

steel. EMT fittings shall be interlocking compression type of cadmium-plated

malleable iron or zinc coated steel, or stainless steel. No die cast, set screw and
indenter type fittings shall be used. Acceptable manufactures are Allied,

Wheatland or equivalent.

Aluminum conduit shall be rigid, heavy wall aluminum. Acceptable

manufacturers: Anaconda, Kaiser, VAW, or equivalent.

Flexible Metal Conduit

a. Flexible Metal Conduit shall be constructed of one continuous length of
U.L. Approved electro-galvanized, spirally wound steel strip with
interlocking convolutions and interior surfaces free from burrs and sharp
edges.

b. Flexible metal conduit shall be "liquid-tight" with PVC jacket. Acceptable
Manufacturers: Alflex, Electri-Flex, Thomas & Betts, or equivalent.

c. Flexible metal conduit installed in hazardous, NEMA 7, Class I Div | areas
shall be UL Listed, and shall have a bronze or stainless steel braid covering
over a flexible brass inner core. Packing shall be woven cotton braid
impregnated with asphalt.

d. Acceptable manufacturer: Crouse-Hinds, Killark, Thomas & Betts-XP
Series, or equal.

Non-Metallic (P.V.C.) Conduit shall be Schedule 80, extra heavy wall or

Schedule 40, heavy wall and UL Listed for the use intended. Acceptable

Manufacturers: Carlon, Harrison, or equivalent.

P.V.C. Coated Rigid Galvanized Steel Conduit. Acceptable Manufacturers:

Rob-Roy "Plasti-Bond", Ocal, or equal.

a. The PVC Coated Rigid Galvanized Steel conduit, shall fully comply with
the following industry listings and manufacturer's standards without
exception prior to PVC coated application, shall conform to Federal

13089K