Project Number: 228730 WWTE SCADA Upgrades

Issue Date: August 2017 Nashua, NH
L. Nameplates
1. All panels and panel devices shall be supplied with suitable nameplates

that identify the panel and individual devices as required. Each device
nameplate shall include up to 3 lines, with the first line containing the
device tag number as shown on the Drawings, the second line containing a
functional description, and the third line containing a functional control
description.

2. Unless escutcheon plates are specified or unless otherwise noted on the
Drawings, nameplates shall be 3/32-inch thick, black and white, Lamacoid
with engraved inscriptions. The letters shall be black against a white
background. Edges of the nameplates shall be beveled and smooth.
Nameplates with chipped or rough edges will not be acceptable.
Nameplates shall be affixed to the panels using #4-40 threaded stainless
steel button head hex screws.

3.02 CONTROL PANEL QUALITY ASSURANCE

A.

Panel Shop shall, upon fabrication of the control panels, apply power to each
panel to ensure that panels are wired correctly, and all devices contained within
the panels power up properly. Panel Shop shall provide written confirmation to
the Engineer that a power up test was completed.

Panel Shop shall complete a point-to-point wiring checkout for all wiring
contained in the control panels, and correct any errors or omissions found during
that process. Panel Shop shall provide written confirmation to the Engineer that
checkout was completed.

Panel Shop shall provide advance notice to the Engineer that control panel
fabrication is complete, and shall make the control panels available in their
facility for completion of the Factory Acceptance Test by the Engineer or System
Integrator. Panel Shop shall not ship control panels prior to execution of the
Factory Acceptance Test, unless indicated in writing by the Engineer.

3.03 INSTALLATION AND MOUNTING

A.

Provide all labor, tools, material, and equipment required to mount the SCADA
Panel, Intrinsic Barrier Panel, and/or other panel(s) in the locations shown on the
Drawings, in accordance to manufacturer-recommended mounting practices. The
location of panels shown on the Drawings is approximate only. Exact location
shall be as approved by the Owner or Engineer during construction. Obtain in the
field all information relevant to the placing of process control Work and in case of
any interference with other Work, proceed as requested by the Engineer.

All control panels shall be powered up upon installation, and all field wiring shall
be tested for proper termination. All analog signals shall be simulated for a
full-scale 4-20ma test.