Project Number: 228730
Issue Date: August 2017
WWTE SCADA Upgrades
Nashua, NH
B. Prepare enclosure mounting surfaces to be smooth, level, clean and free of debris.
C. If a console or panel is removed or demolished then provide grinding to level
floor surface. Provide grinding to level floor surfaces within 2 inches of newly
installed enclosure if smaller than previously existing enclosure.
PART 2-— PRODUCTS
2.01 CONTROL PANEL COMPONENTS
A. The following table contains control panel components and recommended
manufacturers for each component.
Control Panel Manufacturer (or Comments
Components approved equivalent)
Enclosures Hoffman Shall be suitable for use in the environments that
Hammond they will be located (NEMA, NFPA, etc.)
Saginaw
Programmable Logic Refer to Section 40 63 43, Programmable Logic
Controllers (PLCs) Controllers
Operator Interface Refer to Section 40 63 43, Programmable Logic
Terminals (OITs) Controllers
Wireway Panduit
Hoffman
DIN Rail Allen Bradley
Phoenix Contact
Radio Equipment Match existing Site standards as necessary.
Terminal Blocks Allen Bradley Utilize 2-tier terminal blocks wherever possible to
Phoenix Contact conserve panel space.
Entrelec
Terminal Block Fuse Allen Bradley Specify fuse holders with blown fuse indicators.
Holders Phoenix Contact
Entrelec
Circuit Breakers Square D
Allen Bradley
120VAC Surge Phoenix Contact
Suppressors Square D
WOODARD & CURRAN
CONTROL SYSTEM EQUIPMENT PANELS AND RACKS
40 67 00-5