Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH
C.
D.
Device Plates
1. Device plates for receptacles shall be stainless steel.
Weatherproof Device Plates
1. Provide weatherproof device plates where indicated and required.
2. Interior and Exterior Wet Locations: Device plates for interior and exterior
wet locations shall be die-cast aluminum, gasket, with corrosion resistant
screws to match plate cover finish. Provide weatherproof receptacles with
vertical “in-use” covers for complete weatherproofing when plug is
inserted.
2.02 CONTROL RELAYS
A.
mo Oo 8
Control Relays: Allen Bradley Bulletin 700-H Series, Square D or equal.
120V coil as required or as indicated.
Number of poles as indicated or required.
Electrically Held, except as noted.
Enclosure shall be NEMA-1, except as noted.
2.03 MOTOR CONTROL RELAYS/CONTACTORS
To Oo FP YP
7
G.
Allen Bradley, Square D or equal.
120V and 277V coils as required or as indicated
Number of poles as indicated or required.
Horsepower rated for connected motor.
Electrically Held, except as noted.
Enclosure shall be NEMA-1, except as noted.
600V Rated.
2.04 CONTROL STATIONS
A.
Enclosures shall be common or grouped mounted for devices in the same location.
Devices shall include front mounted nameplates identifying function.
Subject to compliance with requirements, provide control stations by one of the
following:
WIRING DEVICES
WOODARD & CURRAN 26 27 26-4