Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH

F. Any cable which fails the insulation tests or which fails when tested under full
load conditions shall be replaced with new cable for the full length and retested at
no additional cost to Owner.

G. The below grade service or feeder splice shall be water immersion Megger tested.
Each splice shall be immersed in a grounded water immersion bath for 24
continuous hours prior to and during the test. Criteria for failure shall be as
described for cable above.

END OF SECTION

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES