Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH

2. WC-7 Cross Linked Thermosetting Polyethylene Insulated Wire and Cable
for the Transmission and Distribution of Electrical Energy

3. WC-8 Ethylene Propylene Rubber Insulated Wire and Cable for the
Transmission and Distribution of Electrical Energy

E. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)

COMPLIANCE
1. Standard 82 Test Procedure for Impulse Voltage Tests on Insulated
Conductors

1.04 SUBMITTALS

A. Furnish manufacturer's product data, test reports, and materials certifications as
required.
B. Submit the following in accordance with Conditions of Contract and Division 26

specification sections:

1. Product data for electrical wires, cables, and connectors.
2. Product data for Megger insulation testing instrument.
3. Report sheets for Megger testing.

1.05 DELIVERY, STORAGE, AND HANDLING:

A. Deliver wire and cable properly packaged in factory fabricated type containers, or
wound on NEMA specified type wire and cable reels.

B. Store wire and cable in clean dry space in original containers. Protect products
from weather, damaging fumes, construction debris, and traffic.

PART 2 - PRODUCTS
2.01 MATERIALS

A. General

1. Provide factory-fabricated wires of sizes, ampacity ratings, and materials
for applications and services indicated. Where not indicated, provide
proper wire selection as determined by Installer to comply with project's
installation requirements, NEC and NEMA standards. Select from the
following UL types those wires with construction features which fulfill
project requirements:

2. Provide color-coding for phase identification as specified herein.