Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH
Each nameplate inscription shall identify the name of the equipment, function
and, when applicable, the position. Nameplates shall be melamine plastic, 0.125
inch thick, black with white letters. Surface shall be matte finish. Corners shall
be square. Accurately align lettering and engrave into the core. Minimum size of
nameplates shall be one by 2.5 inches. Lettering shall be a minimum of 0.25 inch
high normal block style. All electrical equipment shall be labeled with the
following:
1. Panel Name
2. Fed from “Panel Name” & “CKT #”
3. Amps
4. Volts
5. Phase
1.17 ARC FLASH LABEL
A. Provide arc flash labels for all electrical equipment with operating voltages greater
than 50 volt per NEC 110.16.
1.18 WARNING SIGNS
A. Exterior warning and caution signs shall be weather resistant, nonfading,
preprinted cellulose acetate butyrate signs with 20 gauge, galvanized steel
backing, with colors, legend, and size appropriate to the location.
B. Interior warning and caution signs shall be aluminum signs with preprinted baked
enamel finish and punched for fasteners. Colors, legend, and size appropriate to
location.
1.19 WIRE AND CABLE MARKERS
A. Underground line marking tape shall be permanent, bright colored, continuous
printed, metal backed, plastic tape compounded for direct burial service not less
than 6 inches wide. Printed legend indicative of general type of underground line
below.
B. Wire labels for wires smaller than No. 4. shall be vinyl or vinyl cloth,
self-adhesive, wraparound, wire markers with preprinted numbers and letters.
Wire sizes No. 4 and larger and multi conductor cables shall be marked with one-
piece, nylon locking marker ties equal to Panduit PLM Series.
PART 2 - PRODUCTS
2.01 MATERIALS
COMMON WORK RESULTS FOR ELECTRICAL
WOODARD & CURRAN 26 05 00-9