Project Number: 228730 WWTE SCADA Upgrades
Issue Date: August 2017 Nashua, NH
1.08
1.09
1.10
6. Check with Engineer before installation of Work for outlets not specified
as to location or for Work that interferes with other trades.
FLASHING, CUTTING, FIREPROOFING AND WATERPROOFING
A.
Flashing around all electrical items penetrating roof or exterior walls shall be the
responsibility of the Contractor.
All cutting of surfaces, including core drilling of walls and slabs, shall be done by
the Contractor.
Patching shall be done by the Contractor.
The Contractor shall fireproof, waterproof and seal all openings in slabs and
walls.
PRODUCT DELIVERY, STORAGE, AND HANDLING
A.
Protection. Use all means necessary to protect electrical system materials before,
during and after installation and to protect the installed Work and materials of all
other trades.
Replacements. In the event of damage, immediately make all repairs and
replacements necessary to the acceptance of the Engineer and at no additional cost
to the Owner. If any apparatus has been subject to possible injury by water, it
shall be thoroughly dried out and put through such special tests as directed by the
Engineer, at the cost and expense of the Contractor, or shall be replaced by the
Contractor at his own expense.
Protect the Work of other trades. Restore any damage caused to other trades to the
condition existing prior to damage at no additional cost to the Owner.
Investigate each space in the building through which equipment must pass to
reach its final location. If necessary, the manufacture shall be required to ship his
material in sections sized to permit passing through such restricted areas in the
building.
WORK PERFORMANCE
A.
Electrical work shall be accomplished with all affected circuits or equipment de-
energized. When an electrical outage cannot be accomplished in this manner for
the required work, the following requirements are mandatory:
1. Electricians must use full protective equipment (i.e., certified and tested
insulating material to cover exposed energized electrical components,
certified and tested insulated tools, etc.) while working on energized
systems in accordance with NFPA 70E.
COMMON WORK RESULTS FOR ELECTRICAL
WOODARD & CURRAN 26 05 00-6