Project Number: 228730 WWYTE SCADA Upgrades
Issue Date: AugustSeptember 2017 Nashua, NH
B. Install minimum one 4)-++*_l-inch conduit, or as otherwise noted or detailed on
the Contract Drawings, from accessible ceiling space to each outlet indicated.
Provide and install required conduit wire, pullboxes, and accessory items to
accomplish the work involved in providing the new network service as shown on
the Drawings. All boxes, raceways, equipment, etc. shall be bonded in accordance
with NEC.
Coordinate service work with the Owner.
Terminate all cables at the origination and outlet end of all cables. Tag all cables
at the terminal block end to designate the locations of the outlets. All cables shall
be bundled neatly, tie-wrapped and dressed appropriately.
Obtain all permits, pay all fees and provide all materials and labor necessary for
interfacing with utility equipment to install data or internet service.
Furnish and install all conduit, boxes, outlets and low voltage wire and accessory
items necessary to accomplish the work detailed herein or in the Drawings.
Concealed wiring in dry locations above ceilings, except as specifically noted may
be run without conduit. Wiring in all other locations shall be installed in approved
raceways.
1. In ceiling return air plenums, use Teflon air Plenum type cable, unless
used inside conduit or tubing sleeve.
2. Provide bushing at each end of conduit run.
3. Cable shall be installed as tight to roof deck as possible, parallel and
perpendicular to beams, joists, etc.; if run perpendicular beams, joists, etc.,
provide necessary hardware for proper support.
4. Cables shall be properly secured in place. Support cables above accessible
ceiling, using spring metal clips or approved cable ties to support cables
from structure.
5. Do not support from ceiling suspension system. Do not rest cables on
ceiling panels. Do not drape over ductwork or between bar joists.
6. Wiring shall not be run diagonally wherever possible and shall be cabled
neatly.
In areas above suspended ceilings where cables are run without conduit, supports
shall be provided at intervals not to exceed 5 feet and shall be independently
attached to building structure.
ADDENDUM NO. 3 COMMUNICATIONS